Serving Kennesaw, Acworth, Marietta, and all other Cities in the Greater Atlanta Area 

 

 

 

 

 

 

Call - 678 567-2055

 

 

 

 

 

 

 

For a limited time, a free Thermal Imaging Scan will be provided for each Home Inspection

 

 

 

 

 

 

Standard Home Inspection

 

Home

Provided Services
Standard Home Inspection
Thermal Imaging
Radon Detection
Maintenance Inspection
Our Credentials
Contracts
Sample Report
About ASHI
About GAHI
About Building Code Certification
Information For Sellers
FAQ
Contact Us

 

 

 

All home inspections are preformed to the strict Standards of Practice, and Code of Ethics of the American Society of Home Inspectors.  

Grounds

1 - Driveway
Concrete often cracks due to drying and shrinkage. Excessive cracks often create trip hazards and correction may require replacement of the concrete. Asphalt driveways need regular maintenance and resealing.

2 - Sidewalks
Walks can become damaged by tree roots and settlement. Excessive cracks can often be repaired by replacing sections of the sidewalk.

3 - Retaining Walls
These walls are used to stabilize steep banks and control soil movement. Water that is allowed to collect behind the wall can exert pressure causing the wall to move. Drainage provisions are often not evident with a visual evaluation. Sometimes efflorescence ( a white powdery substance) is present on the wall due to no or blocked drainage. Retaining walls should appear straight or tilt slightly toward the earth they support. Walls that are cracked or leaning will need structural evaluation and repair.  Any section of retaining wall that is  higher than 30" above the surrounding ground should have a guardrail that is at least 36" tall.

4 - Patio
Patios are similar to driveways and sidewalks with respect to cracks and movement. Patios should be installed to drain water away from the house.

5 - Patio Cover
Structures are built over decks, patios and porches to provide protection against the rain and shade from the sun. These structures are considered to be a structural element and require proper design and attachment.  If the cover is integral with the house roof, information will be provided in the roofing section of the report.

6 - Wood Decks/Porches
Properly installed flashing is needed to prevent damaging water from weakening the decks attachment to the structure of the home. Improperly installed flashing  is usually the main cause of deck collapses during high occupancy conditions such as parties. All support bracing, joist, beams, and post should be present and properly installed.  Decks that are higher than 30" above the surrounding ground will need a guardrail that is at least 36" tall. Newer installations should not have any space in the railing that is larger than 4" in width. Handrails for steps to decks and porches need to be easily gripped. Wood decks or porches should be supported by concrete footings and clearance of the wood to the soil is critical to avoid deterioration.   Decks or porches with waterproofed surfaces need regular maintenance and resealing approximately every three to five years to prevent cracking and deterioration. If carpet or other material covers the deck, we recommend removal for evaluation.

7 - Fences and Gates
Our evaluation of fences is limited to those areas which hay directly have an affect on the condition of the house. Fences that are surrounding pools must be of sufficient height for safety. Each jurisdiction has safety height standards. Gates that enter pool areas must be self-closing and latching.

Top of page


Exterior

8 - Exterior Stairs
Uneven steps are a trip hazard which should be corrected. The difference in the distance between one step and another should be no greater than 3/8 inch. Handrails should be secure and have a grip able surface. Two by four inch or two by six inch boards are not considered appropriate for handrails unless they are routed with a grip. Current standards call for narrow clearances between rails such that a four inch sphere may not pass through. Older rails had larger openings when installed and upgrading should be considered for child safety.

 

9 - Exterior Walls
Exterior wall coverings protect the wall framing and interior finishes from the weather. Any openings or penetrations in the covering should be properly sealed with an appropriate flashing or sealant.. Earth should not touch the wall covering and a clearance of approximately 4 to 6 inches should be maintained.  If the wall system is E.I.F.S., we recommend a fully certified inspection for further information.

10 - Trim
Trim includes the eaves, soffits, facia and moldings around the exterior. The eave is the portion of the roof that overhangs the wall. Soffits are enclosed eaves and should be properly vented to prevent moisture damage. Facia is the board installed at the end of the eave to give the house a finished appearance. Many times, water running off the roof flows onto this board causing damage.

11 - Chimney
In this section of the report you will find our evaluation of the exterior of the chimney. Spark screens and rain caps are used over the chimney flue to prevent sparks escaping and water entering the fireplace. The top cement covering of the brick also diverts water from damaging the masonry and cracks should be sealed for protection.

12 - Fire Sprinklers
Our check for fire sprinklers is limited to identifying their presence, and a strong recommendation to become familiar with their operation, and water cut-off location. Adequate coverage is also not included.

13 - Hose Faucets
If hose faucets are winterized and shut off, they cannot be inspected. Anti-siphon devices for hose faucets prevent any contaminated water from being siphoned back into the house supply. These are easily installed if none are provided.

14 - Gutters and Downspouts
Gutters should always be clean and firmly attached to the home.  Downspouts should also be firmly attached and should always promote the flow of damaging water away from the home and its foundation. Flat roofs that drain into area drains should be provided with a second drain system that will operate should the primary drain become blocked.

Top of page

 

Foundation

Lot Drainage
Raised Foundation

 

Slab on Grade

Basement

 

Note: The inspection of the foundation components is limited to visible and accessible areas only. Finished or partially finished basements limit access. Moisture in basements and crawlspaces is a common problem and any indication of water penetration should be reviewed. Control of rain and surface water around the house is critical to keeping foundation areas dry.

Moisture can cause decay and deterioration to wooden components and excessive water can damage foundations. Regular inspections and constant water management is advised.

15 - Lot Drainage
16 - Slab on Grade
17 - Raised Foundation
18 - Basement

 

 

Top of page

Roof

19 - Asphalt Shingles/Wood Shingles

Asphalt Shingles: Commonly called composition shingles, this material has a typical life expectancy of 12 to 25 years, depending on many factors. Roof covering is checked for damage, aging, and qualify of installation.

Wood Shake and Shingles: Wood roofs will typically last 20 to 35 years depending upon the thickness and quality. Annual maintenance is required on wood roofs which consists of replacing the weather-damaged shakes. In some areas the constant moisture can cause the wood to deteriorate. Care against fire is advised.

20 - Clay and Concrete Tile/Slate/Metal and Fibrous

Clay and Concrete Tile: These materials are very durable and have anticipated life of 30 to 50 years. The tiles, however, are brittle and can be damaged, so the roof cannot be walked on. The inspection is very limited.

Slate: Considered one of the longest lasting roofing materials, slate can endure 50 to more than 100 years. A very brittle and expensive roof, inspections are limited.

Metal and Fibrous: Metal roofing comes in many forms from shingles to panels. Fibrous roofing is a mixture of various materials including cement and perlite.

21 - Built-Up Roofing / Single Ply / Foam

Built-Up Roofing: The surface covering is the distinguishing feature of this roof cover. Maintenance consisting of repairing any worn areas is required. Installed on low slopes, these roofs should be inspected annually due to the potential for poor drainage.

Single-Ply: A relatively new roofing system, single-ply membranes are gaining in popularity. The roof covering consists of large sheets of a rubber or PVC-based compound.

Foam: Polyurethane foam with elastomeric coating. This roof requires periodic re-coating to extend its service life.

22 - Exposed Flashings

Top of page

Plumbing
23 - Main Water Line
The main water supply pipe brings water from the street to the home. Older pipe materials may be 1/2" or 3/4" galvanized steel. This type of pipe corrodes internally and may not deliver the volume of water now needed throughout the house. 3/4" copper or plastic pipe is the minimum currently used in modern construction. Normal water pressure is between 35 and 80 PSL. Excessive pressure can wear on valves, fittings, fixtures and appliances.

24 - Water Supply Lines
Copper, galvanized, plastic and lead piping have all been used at some time for water systems of residences. Old galvanized piping typically requires replacement due to internal restriction. Lead pipes present a possible health hazard if the lead leaks into the drinking water. A form o plastic piping called "polybutylene" has shown defects from the manufacturing and installation process that can cause leaks. Your inspector is only able to tell you of the condition of the visible piping. No water quality tests are performed during this inspection.

25 - Waste Lines
These pipes carry the waste from the house to the sewer system. It is impossible to predict waste line blockages as these can occur at any time during use. Some plastic, "ABS" pipes have shown defects from the manufacturing process and can become weak and break.

26 - Fuel System
Natural gas is delivered to the house through underground pipes and a meter. Some homes have on-site fuel storage that consist of oil or propane fuels and a storage tank. 

27 - Water Heater
Water heaters are sealed systems which contain a great deal of pressure. The TPR (Temperature & Pressure Relief) valve is a device designed to release excessive pressure from the system. There should be a drain pipe attached to this valve which terminates at a safe location away from body contact. Water heaters sometimes make gurgling noises which are typically the result of built up calcium inside the tank.

Top of page


Heating

28 - Description
Our description of the heating system includes where the unit is located and the fuel used to generate the heat. Forced air furnaces and water boilers can operate on gas, oil or electricity. Heat pumps utilize electricity to drive the motors and compressors. Furnace size is listed for reference only, if available, and no calculations are performed during this inspection to determine the adequacy or efficiency of the heating system.

29 - Condition
Systems are tested using normal homeowner operating controls. If pilots or circuit breakers are off at the time of the inspection, the inspector will not ignite or activate the system. You can contact the utility provider for evaluation of the heating system.

30 - Venting
Fuel burning appliances exhaust the products of combustion to the exterior through vent pipes. Vent pipes utilize caps to prevent moisture entry and to stop back drafting. Back drafting means that the products of combustion are escaping into the home instead of venting to the exterior.

31 - Combustion Air
When fires burn, they consume oxygen. Fuel that burns completely is harmless and creates only carbon dioxide. Fuel burning appliances must be provided with a constant source of fresh air for the fuels to burn properly. If air is not provided to the fire, incomplete combustion may occur which could produce carbon monoxide. Be sure not to block any air vents around or near your heating systems. Also be advised that maintaining clean air filters is important not only to the air you breathe, but to the operation of the unit as well.

32 - Burners
It is impossible to see an entire heat exchanger inside most furnaces, so this inspection does not comment on this component. If there is an uneven or unusual flame pattern or there is rust, charring or deterioration in the burner chamber, we recommend a further investigation of the unit.

33 - Distribution
Most heaters utilize some method of moving the furnace generated heat to the rooms which need the heat. Forced air heaters use ducts and registers. Water heating systems use pipes and radiators or convectors. Radiant systems may use pipes or wires if electric. Much of the distribution system will not be visible during this inspection and cannot be judged. For instance, water piping that is buried below or in the concrete floor slab may have leaks that are not detectable without specialized equipment.

Top of page


Cooling

34 - Normal Controls
Normal operating controls are homeowner operated devices such as a thermostat, wall switch or safety switch. Loose thermostats should be secured and thermostats that are not centrally located or on outside walls should be relocated for better furnace performance.

35 - Air Filters
Regular cleaning or changing of air filters is important for proper furnace performance. Dirty filters can cause damage to the heater and waste energy dollars. We do not evaluate the operation of electronic air cleaners but will comment on cleanliness if present.

36 - Heating Notes
Our evaluation of the heating system is visual only and does not include dismantling the unit. A service technician should be consulted for an in-depth evaluation, cleaning and adjustment of the furnace for optimum performance and safety. Most local gas companies will perform a safety check and light gas pilots for their customers prior to the heating season. We also do not evaluate humidifiers built onto the heating unit
.

37 - Evaporative Cooler
Evaporative coolers (commonly called swamp coolers) utilize air flowing across moving water to humidify and cool the house air. Standing water that is left in the unit for extended periods of time can breed bacteria. Evaporative coolers should be drained at the end of each cooling season and cleaned prior to use.

38 - Air Conditioner
Air conditioning systems rely on a constant flow of air through the system to properly operate. Restricted air flow from dirty filters or blocked coils can cause icing on the evaporator coil. This may make the air from the unit appear to be colder but is actually harmful for the system. Compressor units located outside should also be kept clear of air restriction. Trim back shrubs and grasses and don' place anything over the tip of the unit that blocks air flow.

Top of page


Electrical

39 - Electric Service
The electrical service refers to the wires that run from the street or main pole and enter the house either underground or through the rooftop. The number of wires that enter the panel determine the voltage of the service: 2 wires = 120 volt, 3 wires = 240 volt. A home that has only a 120 volt service would be considered out of date by today's standards because larger appliances that operate at 240 volts cannot be utilized. Electrical load and demand calculations are not performed during this inspection.

40 - Main Panel
The capacity of the system is determined by the size of the service wires, the rating of the panel and the size o the main fuse or breaker. Some older panels will have fuses while newer systems use breakers. The main disconnect is used to shut the entire electrical system in the house off in case of emergency. If no main shutoff is provided, no more than six breakers are allowed to be installed.

41 - Conductors
Conductor is the term used for the wires used for electrical installations. Copper and aluminum are common materials used for electrical wiring. The U.S. Product Consumer Safety Commission issues a booklet on the hazards of aluminum wire installations made in the early 1960's to the mid 1970's. Please obtain this information if aluminum is noted.

42 - Sub-Panel
Electrical panels that do not contain the mail service wiring are called sub-panels. Sub-panels are used for a variety of reasons ranging from house size to ease of accessibility. During inspections of homes that are occupied it is possible that a sub-panel might be hidden by pictures or furniture. Please check carefully during your final walkthrough of the house after all belongings are removed.

43 - Panel Notes
This section of the report notes conditions found inside the electrical panels. Repairs to wiring conditions should be performed by qualified trades people due to the inherent hazards.

44 - Wiring Notes
Our inspection of the electrical wiring and fixtures throughout the house will include random testing of outlets and lights. At least one outlet per room, all accessible outlets in the garage and on the exterior, and all outlets within six feet of sinks will be tested for grounding and polarity.

Top of page


Interior 

45 - Entry Doors
Weather-stripping around the entry door keeps cold air from entering the house. If no weather-stripping is provided we recommend it be installed.

46 - Interior Doors
Doors that stick, bind or won't close properly can be adjusted or trimmed to fit. Sometimes however, when doors are out of square and other related conditions are present, it may be an indication of movement in the structure or foundations. If these notes are made, a qualified civil, structural or geo-technical engineer should be consulted.

47 - Exterior Doors
Non-safety glass has been used for years in the sliding glass doors of older homes. You should consider upgrading any non-tempered glass doors throughout your home. At times, it is not possible to determine if glass is tempered.

48 - Windows
Windows are checked during out inspection. The condition of winter storm windows and doors are not part of this inspection. It is not possible to evaluate the seal on thermo pane windows as conditions change from morning to night and season to season.

49 - Interior Walls
In occupied homes, not all portions of all walls will be exposed to view. After the occupants remove all of their belongings, it is wise for you to conduct a final walkthrough of the home. look carefully at areas that were not visible during this inspection.

50 - Ceilings
Moisture stains on ceilings can come from a variety of sources: plumbing leaks, roof leaks and condensation to name a few. At times it is not possible to determine the cause of a stain. Some older acoustic sprayed ceilings have contained asbestos in the past. Only laboratory testing will accurately reveal asbestos and this testing is not included in the inspection fee.

51 - Floors
Our evaluation of the floors in the home is to identify major defects where visible. Stains or odors may be hidden and are not part of this inspection. Once furniture and belongings are removed you will be able to view the condition of floor coverings. Do a careful check on your final walkthrough.

Top of page


 

52 - Fireplace
Our evaluation of the fireplace does not include a smoke test. Some fireplaces emit smoke into the house during use. If this occurs, a qualified chimney sweep should be contacted for remedy.

53 - Interior Features
A - Central vacuum
B - Ceiling fan
C - Interior stairs
D - Stair handrail
E - Wet bar faucet
F - Wet bar counter
G - Plumbing

53 - Smoke Detector
Smoke detectors are most effective when located on each floor, in bedrooms and in hallways outside of bedrooms. These units are tested by pushing the test button. Carbon monoxide detectors are new devices that should be considered if fuel burning appliances are installed in the house.

55 - Laundry
Washing machines and dryers are not moved or operated during our inspection of the laundry area. Areas behind and under the machines cannot be judged.

56 - Attic
A - Roof framing
B - Ceiling framing
C - Ventilation
D - Insulation
E - Plumbing vent pipe
F - Recesses ceiling light
G - Attic access

Top of page


Garage

57 - Floor
Garage floors should be constructed of non-flammable materials. Carpeting or other floor coverings should be removed. The floor should also be sloped to drain out the overhead door.

58 - Firewall/Ceiling
A wall or ceiling that separates the garage from the house is considered a fire separation. The coverings of these areas should not have large holes. It is typically not possible to determine the rating of these coverings.

59 - Ventilation
Ventilation for the garage becomes critical when fuel burning appliances are installed in the garage. These appliances require air for proper combustion.

60 - Door to Living Space
The door that enters the house from the garage is considered a fire separation door and should be solid wood, solid core or rated for that location. Pet doors are not allowed.

61 - Exterior Door
Sometimes hollow core doors are installed in this location and moisture will delaminate the door skin at the bottom.

62 - Vehicle Door
Garage vehicle door types vary from roll-up to tilt-up to sliding. Older door hardware springs are considered unsafe if safety catches arm wires are not provided. For safety, upgrading is recommended for older hardware.

63 - Automatic Opener
Garage door opener remote controls are not tested. If a door hits an obstruction during closing is should reverse automatically for safety. Older openers were not equipped with this safety function.

64 - Electrical
The garage is a common area for electrical wiring, lights and outlets to be added. All added electrical requires a permit. One of the most common mistakes is using extension cords to power lights or garage door openers.

Top of page


Kitchen

66 - Kitchen Sink
Our evaluation of the sink includes turning on the faucet. We check functional flow and look for obvious leaks at the handle and spout. We also run water looking for functional drainage; however, drain lines can become blocked at anytime, and this condition cannot be predicted. Under the sink we check for leaks, rust and corrosion of the sink, drain and supply piping.

67 - General Features
General features include: condition of counters, cabinets, flooring, windows, ceiling and light fixtures. Many times dishes and belongings will block view of counters and cabinets. These items are not moved during this inspection and you should check these areas during your final walkthrough, and after the occupants have moved out.

68 - Garbage Disposal
Garbage disposals can rust and corrode internally. It is difficult to verify the condition of the interior of the unit. If the unit vibrates excessively or makes unusual noises, matter may be lodged inside or blades may be damaged. Sometimes repair is simple, while other times replacement may be required.

69 - Range/Oven/Cook top
The elements and burners of ovens, ranges and cook tops are checked for functionality only. Calibration of thermostats is beyond the scope of this inspection.

70 - Dishwasher
Our inspection of the dishwasher includes the general condition of the unit, dish racks and door seals. The condition of the pump and motor is not determined since the dishwasher is not disassembled. Racks that are rusted can usually be replaced.

71 - Special Features
Special features, if inspected, are tested just as any homeowner would use the device or appliance. No disassembly or special test equipment is used. If there is no trash in a compactor we turn the unit on; however, this does not verify compacting ability. If we operated a microwave we will heat a glass of water for one minute although heating ability varies between units.

Top of page


Bathroom

72 - Toilet
Toilets that are loose at the base or at the tank connection pose the possibility of leaking. Sometimes the wax seal at the floor must be replaced to prevent leakage on the floor or below the house.

73 - Sink
The water shutoff valves below the sink are not tested during this inspection. Many times these valves have not been used for some time and can leak if turned. This is a common occurrence.

74 - Ventilation/Heat
Bathrooms that contain a tub or shower need ventilation either through a window or mechanical exhaust vented through the roof or wall.

75 - Bathtub
Our evaluation of the bathtub consists of the visible and accessible areas only. Many times the drain and supply piping are not accessible and cannot be judged. Maintaining the caulk and grout in good condition is important to avoid leakage. We do not fill the tub to overflowing to check the overflow drain connection. If a whirlpool is installed we test the equipment using normal operating controls. Sometimes access to the pump and jet piping is not possible and they cannot be inspected.

76 - Shower
Shower enclosures should be properly caulked and maintained to avoid leakage. It is often difficult to determine if glass enclosures are tempered safety glass. All non-safety glass is considered a potential hazard and upgrades should be considered.

Top of page

Fidelity Home Inspections, LLC     678 567-2055     johnbadger@fidelityhomeinspections.com